If you use the function TrnSetScale to set
all the scales on a trend at once, the function will not set any of
the scales. For example if you call as follows
TrnSetScale(40,-1,-1,0) has no effect on the trend when executed.
When the same function is called for individual pens (eg.
TrnSetScale(40,2,-1,0) it works perfectly.
CIT has confirmed this to be a problem in Citect for Windows versions 1.00 to 2.01. This problem has been fixed in version 2.10 and later. |
Solution: |
You may work around this problem by setting each pen individually or by upgrading to version 2.10 and later. |