Applies To: |
|
Summary: |
Using TrnPrint() to print out trend data,
If you are not Using all you get the Following Hardware alarm
"Trend General Trend Pen Not Found SingleTrend Pen No . 8".
CIT has confirmed this to be a problem in Citect for Windows versions 1.00 to 2.10. This problem has been fixed in version 3.0 and later. |
Solution: |
Use the function ErrSet() to disable the hardware errors across the call to the TrnPrint() function or use version 3.00 or later. |
Keywords: |