Applies To:
  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

Summary:
The alarm threshold display formats eg {HighHigh,n} are not updated on the alarm display page when the AlarmSetThreshold() cicode function is used. The actual threshold values on the alarm server are updated correctly, however they are not updated on the Citect clients alarm display pages.

CIT has confirmed this to be a problem in Citect for Windows versions 1.00 to 2.10. This problem has been fixed in version 3.00 and later.

 

Solution:
Use Citect for Windows version 3.0.

See also Q1494.

 

Keywords:
 

Attachments