Applies To:
  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

If you are logging alarms to a dBASE device and Citect cannot open that device you may get a GPF. This may occur if Citect can open the device at startup and the device is lost while Citect is running and then Citect tried to reopen the device.

CIT has confirmed this to be a problem in Citect for Windows versions 1.00 to 2.01. This problem has been fixed in version 2.10 and later.


Use version 2.10 or later.

1066 Trend redundancy blows up for a large number of trends "Trend redundancy will cause a crash if trend records occupy two or more blocks.(one block is about 64 k)