Applies To:
  • CitectSCADA 1.20 2.00 2.01

Summary:
If the following timeouts for the CiNet (LLC) driver are set too big they do not work correctly. If [LLC]SerialConnectTimeout and SerialSendTimeout > 32767 ms then CiNet does not work if.

CIT has confirmed this to be a problem in Citect for Windows versions 1.11 to 2.01. This problem has been fixed in version 2.10 and later.

 

Solution:
You should only need to set this long a timeout for very large or slow networks. If required upgrade to version 2.10 or later. 