Applies To: |
|
Summary: |
If a CiNet (LLC) session goes online and
offline many times the LLC driver will eventualy run out of read
buffers and stop reading incomming data. Once the LLC driver has
run out of buffers all incomming data will stop and the CiNet will
fail by every session going offline. This will occur after the
maxpending number of DCBs (CTDRV_READ or CTDRV_UI_READ).
CIT has confirmed this to be a problem in Citect for Windows versions 1.11 to 2.01. This problem has been fixed in version 2.10 and later. |
Solution: |
Upgrade to version 2.10 or later. |
Keywords: |
Related Links