Applies To: |
|
Summary: |
Question: We have a Citect system
communicating with a Koyo/TI405/DL405 (Direct Logic 405) PLC via a
Facts Engineering F4-SLV-TW module using TIWAY Local Line. The
F4-SLV-TW is supposedly 100 percent compatible with a standard
TIWAY NIM. The system seems to work OK except for a GENERAL ERROR
flagged whenever more than 14 V memory registers are read by
Citect.
It would be appreciated if you could look at this configuration and let me know if it is 100 percent compatible with the Citect TIWAY driver? |
Solution: |
This hardware solution you have described
seems to be not 100 percent compatible with the existing Citect
TIWAY driver. This problem is that the NIMs you are using cannot
service as large a request as the standard TI NIMs, so whenever
Citect tries to read more than 14 registers these NIMs return an
error. The max request size for Tiway can be modified in Citect so
that it will be compatible with these modules or NIMs.
Modify the TIWAY entry in the C:\CITECT\BIN\PROTDIR.DBF file as follows: TAG FILE BIT_BLOCK
MAX_LENGTH OPTIONS Next add the following parameter to the Citect.INI file. [TIWAY] In some cases you may also need to set the following parameter to slow down the Citect requests to the PLC [TIWAY] |
Keywords: |
Related Links
Attachments