Question: When I display the runtime and the starts from my accumulators they don't update correctly. 

Solution:
The accumulators are being updated correctly however to optimise the communication from Citect to the physical I/O Device, accumulators are only updated every 10 minutes. This reduces the number of writes to the physical I/O Devices. Accumulators are also written to the physical I/O Devices when Citect shutdown. If you want you accumulators to be updated at a faster rate then adjust the [Accumulator]UpdateTime parameter. 