Question: I have upgraded to Citect Version 3.00 and have noticed that there is a new project IncV2 in my Citect user directory. What is this project and why isn't added to my Master.dbf file? 

Solution:
The IncV2 project is a project included in Version 3.00 for compatibility with Version 2.xx. Include this project in any project in which you wish to have access to the Version 2.xx default pages (hardware, alarm etc....). If you have done a fresh installation of Citect this project will be put in the new Master.dbf file that comes with Citect Version 3.00. However if you have upgraded from a previous version of Citect the IncV2 is not in Master.dbf file. This is because during an upgrade any replacement of the Master.dbf file would mean that access to existing projects would be lost. If you have upgraded and want access to the IncV2 project you will have to manually add this record to the Master.dbf file.

If you have upgraded from a previous version of Citect and want access to the IncV2 project you will have to add the following record to the Master.dbf file. This can be done with excel or any other database editor that read .dbf files. See Q1095