The board memory address and interrupt
number are set via dip switches.
Boards
form
|
|
Board name: |
User supplied unique
name
|
Board type: |
TIWAY |
Address: |
Board's memory start
segment (in hexadecimal). 0xC800 to 0xDF00 in 0x100 (4K)
increment.
|
I/O Port: |
not used
|
Interrupt: |
Board's interrupt
request line (3, 4, 5, 9, 10, 11, 12 or 15).
|
Special Opt: |
not used
|
Ports
form
|
|
Port name: |
User supplied unique
name
|
Port number: |
not used
|
Board name: |
Use the "Board
name" from the Boards form |
Baud rate: |
not used
|
Data bits: |
not used
|
Stop bits: |
not used
|
Parity: |
not used
|
Special Opt: |
-sN -
Configure the adapter as an HIU with secondary address N. The
default is 0, which configure the adapter as a MHIU.
-mN - Set Maximum of secondary address for the
network to N.
-r - Use psuedo redundancy. |
I/O Devices
form
|
|
Name: |
User supplied unique
name
|
Number: |
Network wide I/O
device number
|
Address: |
PLC unit number
|
Protocol: |
TIWAY |
Port name: |
Use the "Port
name" from the Ports form |
Citect.ini option
[TIWAY]
WarningLevel = 0
All warning are noted. Set to 5 to ignore all non-fatal
warning.
InterruptService = 1
Service hardware interrupt immediately.
Standard citect.ini options
[TIWAY]
MaxPending = 54
Block = 64 bytes
Retry = 0
Delay = 0
TimeOut = 2000 milliseconds
PollTime = 0
WatchTime = 30 seconds
Files
- TIWAY.DLL Tiway Card Driver for windows
- TIWAY.DBF Tiway variable template
TIWAY Variables
Digital
|
|
X1 |
Discrete Input |
Y1 |
Y1 Discrete Output |
C1 |
Control |
Integer
|
|
V1 |
Variable |
WX1 |
Packed Discrete Input |
WY1 |
Packed Discrete
Output |
TCP1 |
Timer Counter Preset |
TCC1 |
Timer Counter Current |
Real
|
|
LKC1 |
Loop Gain |
LTI1 |
Loop Reset Time
(minutes) |
LTD1 |
Loop Rate Time
(minutes) |
LHA1 |
Loop High Alarm Limit |
LLA1 |
Loop Low Alarm Limit |
LPV1 |
Loop Process Variable |
LPVH1 |
Loop PV High Limit |
LPVL1 |
Loop PV Low Limit |
LODA1 |
Loop Orange Deviation Alarm Limit |
LYDA1 |
Loop Yellow Deviation Alarm Limit |
LTS1 |
Loop Sample rate (seconds) |
LSP1 |
Loop Setpoint |
LMN1 |
Loop Output (percent) |
LERR1 |
Loop Error |
LMX1 |
Loop Bias |
LHHA1 |
Loop High-High Alarm Limit |
LLLA1 |
Loop Low-Low Alarm Limit |
LRCA1 |
Loop Rate-of-change Alarm Limit / Minute |
AHA1 |
Alarm High Alarm Limit |
ALA1 |
Alarm Low Alarm Limit |
APV1 |
Alarm Process Variable |
APVH1 |
Alarm PV High Limit |
APVL1 |
Alarm PV Low Limit |
AODA1 |
Alarm Orange Deviation Alarm Limit |
AYDA1 |
Alarm Yellow Deviation Alarm Limit |
ATS1 |
Alarm Sample rate (seconds) |
ASP1 |
Alarm Setpoint |
AERR1 |
Alarm Error |
AHHA1 |
Alarm High-High Alarm Limit |
ALLA1 |
Alarm Low-Low Alarm Limit |
ARCA1 |
Alarm Rate-of-change Alarm Limit / Minute |
|