Applies To:
  • CitectSCADA 3.00

The incremental compile on Version 3 does not count the IO correctly in some cases. As a result, the error "Point Limit Exceeded" can be displayed erroneously at compile time even though the IO count is below the licence key limit. 

If you are experiencing this problem, deselect the incremental compile option (from Options in the File menu in the Project Editor). Do a full compile. After the full compile is completed you can select the incremental compile option again.