Applies To:
  • CitectSCADA 3.00

Summary:
Some sites are experiencing a problem where alarms and reports are printing up to 15 minutes after becoming active or being executed.  

Solution:
CIT has confirmed this to be a problem in Citect for Windows version 3. We are researching this problem and will post new information here as it becomes available.

You may work around this problem by setting the following parameter in the CITECT.INI file:

[DEVICE]
LPTTOSPOOL=0

This option will disable the automatic redirection of LPT devices to the Citect spooler. When this is disabled then Citect will bypass the spooler and print directly to the printer for LPT devices.


Keywords:
 

Attachments