Applies To:
  • CitectSCADA 3.00

SuperGenies do not have to be called from Genies. The SuperGenie substitution functionality can be used directly on pages and templates as well. 

Use the standard SuperGenie syntax on a page or template, and call the Ass....() functions prior to displaying the page or popup. The syntax and Ass functions are used in exactly the same way as for using SuperGenies in conjunction with Genies.

For this kind of SuperGenie substitution, do not create a new SuperGenie, simply place the syntax directly on the page or template. The Edit Bindings and Paste SuperGenie options are not required. All other aspects of SuperGenies remain the same as for making the association through Genies.This application of SuperGenie substitution will be included in the documentation of future major releases of Citect.