Summary:
When I enable the ms clock the communications to the PLC stop working. Various other features stop working and I cannot shutdown Citect either. What is causing this problem. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows version. We are researching this problem and will post new information here as it becomes available.

This will happen when you are using an alternate CITECT.INI file. The real time clock DLL is still looking for the parameters in CITECT.INI while Citect is looking in your alternate CITECT.INI file. To work around the problem use the standard CITECT.INI file.

 