Applies To:
  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

Summary:
If you use the [CtEdit]Backup parameter to enable the file server redundancy and you also have include projects when a failure occurs Citect will not be able to find graphic pages in the include projects. These files include the CTG (graphic pages), CTL (library) and CTT (template). This problem will show up as a failure to display a graphic page when you try to change to a page which is in the include project. 

Solution:
You may work around this problem by copying all the graphic files into your main project directory. For example if you have a main project in directory C:\CITECT\USER\MAIN and a include in C:\CITECT\USER\MYINC, then copy all *.CTG, *.CTL and *.CTT files from the \MYINC directory to the \MAIN directory.

CIT has confirmed this to be a problem in Citect for Windows versions 1.00 to 2.10 This problem has been fixed in version 3.00.

 