Applies To:
  • CitectSCADA 4.20

Summary:
A new parameter to delay the Startup of Citect has been included in version 4.20. However this feature has not be documented in this version. The documentation is detailed below:  

Solution:
[General]

StartDelay=<seconds>

This parameter allows you to delay the startup of Citect for this many seconds. Citect will partly startup and then wait for this delay before continuing to startup. This allows you to delay Citect startup, if it must wait for some other process to starup. This is supported in 32 bit version only.

 

Keywords:
 