Applies To:
  • CitectSCADA 3.x to 3.40 4.20

Summary:
Unsigned Integers do not work on supergenies. It works when using the value on the screen but not when using it in a SuperGenie. TagRead have the same problem. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 3.00 to 4.20. This problem has been fixed in version 5.00 with the addition of the following parameter:

[Code]
Unsigned=0

If [Code]Unsigned is set to 1 then all integers from COMLI and MODCELL units are treated as unsigned.


Keywords:
 