Applies To: |
|
Summary: |
The Citect runtime seems to be displaying the wrong variable tags or no value at all sometimes. Or, a 3rd-party OPC client is failing to read certain variables from Citect's OPC server. |
Solution: |
Some drivers access a table of variable
tags called VARIABLE.DBF. Records in a dBase file marked for
deletion do not get physically deleted until the database is
packed. As a result, a Citect variable tag may reference the wrong
address if deleted records exist in the table. Also, if variables
are defined in an include project, they won't be listed in the main
project's VARIABLE.DBF. As a result, those variables can't be
accessed by this type of driver.
The following drivers require the database to be packed and the variables to be defined in the main project: DDEDRV The DDE driver
OPTOMIST The Opto22 Mistic driver SIXNET The SIXNET driver to SIXNET's Control Room for Windows software STEEPLE The driver to the Steeplechase SoftPLC The following drivers require the database to be packed:
|
Keywords: |
Related Links
Attachments