Applies To: |
|
Summary: |
How can I talk to SYMAX PLC's using MODBUS PLUS? |
Solution: |
A SYMAX PLC can be connected on to a
Modbus Plus network via an NR&D MEB module. The MEB module has
two standard RS422 ports which can be configured to multiple
operating nodes, one of which is a standard RS422 SYMAX port. In
addition, the MEB module contains a Modbus Plus port and a SYMAX
Ethernet port.
With the RS 422 ports configured as standard SYMAX ports, the MEB module performs a SYMAX to Modbus Plus protocol translation. It is therefore possible to have two SYMAX processors communicating via Modbus Plus, provided each SYMAX processor is connected to a MEB module. A Citect system, installed with a SA85 card interface card can be connected via Modbus Plus to a SYMAX PLC by utilising a MEB. MEB Address Configuration: Using the MEB software, configure the RS422 ports on the MEB module with valid SY/NET addresses e.g. Yxx, where Y = 0 or 1 and xx = 00 to 99. Configure the Modbus Plus port on the MEB to a valid Modbus address e.g. zz, where zz = 00 to 64. Ensure the Modbus and RS422 ports do not have the same address e.g. 010 and 10 conflict. SYMAX PLC to SYMAX PLC via Modbus Plus: To communicate using TWRITE or TREAD instructions, use the following address routing: [RS422 Source], [Modbus Source], [Modbus Destination], [RS422 Destination Path] where RS422 Destination Path: CITECT to SYMAX PLC via Modbus Plus: Install the SA85 card in the Citect PC. Include the device driver in the autoexec.bat file. Ensure the device driver is configured with the /r2 and /s5B options. Refer to Citect Design Guide and Q1683 for further information. In your Citect communications configuration, specify the following: Boards: Ports: IO Devices:
|
Keywords: |
Related Links
Attachments