Applies To:
  • CitectSCADA x.x

Summary:
I am communicating to a KOYO PLC via a D4-DCM or F4-SLV-MB Modbus module form Facts Engineering. I need to know how the data types are mapped between the Koyo types and Modbus Types.  

Solution:
D4-DCM & F4-SLV-MB Mapping
 
Koyo Type Modbus Type
X0 12049 (10001 + 800h = 10001 + 2048)
Y0 02049 (00001 + 800h = 00001 + 2048)
C0 03073 (00001 + C00h = 00001 + 3072)
T0 06145 (00001 + 1800h = 00001 + 6144)
V1400 40769 (40001 + 300h = 40001 + 0768)
 