Check the cabling method as per;
- Use an RS232 to 485 converter (NOT RS232 to RS422):
The method for connecting multiple Melsec units is by RS485 two
wire bus as shown in the Melsec manual. This has been tested
however the RS422 method has been known to give problems.
- Bus termination:
The bus is terminated at each end only, if the converter has
terminating resistors then disconnect the terminating resistor from
the first PLC. Terminating resistors are supplied with the Melsec
Computer/Multidrop link modules, eg C24 module and must be added by
the user.
- Ensure correct grounding connections:
The Melsec PLC's requires that SG (signal ground) be interconnected
between the PLCs. Communications will be unreliable without this
connection. They also require shielded cable with the shield
connected to FG (frame ground). Thus a two pair cable is required.
Consult the Melsec Computer/Multidrop link manual.
Notes:
- The impedance of the cable should match the terminating
resistance value (110 ohms as recommended in the manual).
- The protocol mode switch is set to 5.
|