CIT has confirmed this to be a problem in
Citect for Windows versions 3.4/4.2 and 5.0. This problem is fixed
in Version 5.01 and 4.20 Service Pack G Citect.
The problem is due to the fact that the format for the time
field is not sufficiently wide to accommodate AM/PM for the 12 hour
clock. All TrnExportXXX functions are Cicode functions in export.ci
file in the INCLUDE project. Advanced users may widen the TIME
format from 8 to 12, so that there will be room for AM/PM. However,
the users should realize that their changes in the INCLUDE project
will be lost with the installation of a new version.
When 24 hour clock is used the time will be stored correctly as
AM/PM is not needed.
|