Applies To: |
|
Summary: |
If you pass a Trend Tag to the Cicode function TrnGetTable and the tag is not defined in the database then an Application Error (GPF) will occur. |
Solution: |
This problem only occurs for tags not
defined in the database. The problem does not occur for defined
tags.
CIT has confirmed this to be a problem in Citect for Windows versions 5.00. This problem has been fixed in version 5.00 Service Pack A. |