Applies To:
  • CitectSCADA 5.xx

Summary:
When I upgrade my Citect Version 4 project to Version 5, I get the following error when I compile. "FATAL ERROR / Out Of Memory / Limit Point List" 

Solution:
Go to your project directory in DOS and delete *.NDX (These are the Indexes for the Citect DBF files), then go to the Project Editor and PACK the Project (This will re-create the *.NDX files). Now do a full compile.

Keywords:
 

Attachments