If you wish to be able to use Alarm Tags
then the following I/O Device must exist:
Name |
ALARM_TAGS |
Number |
Network wide I/O device number ( choose any number
not used by another I/O device ) |
Address |
( no address required ) |
Protocol |
ALARM ( type this in, as it does not appear in the
dropdown list ) |
Port Name |
ALARM ( type this in, as it does not appear in the
dropdown list ) |
In Citect 7.00 it is no longer necessary to create the alarm
device. To enable alarm property tags, go to the Project Editor |
Servers menu | Alarm Servers. Press F2 to view extended properties,
and set Publish Alarm Properties to TRUE.
|