Applies To: |
|
Summary: |
The Softhub server used by the SQDNET
driver does not currently support multiple requests to a single
device. Therefore this has been prevented in the Citect driver by
ensuring that:
1) the MaxPending driver parameter must be 1 for a port, and 2) multiple logical Citect devices with same physical address must be on the same port. If 1) is not true then a Hardware alarm of value 0x57 will appear, and if 2) is not true then a Hardware alarm of value 0x58 will appear. |
Solution: |
If using the SQDNET driver and want multiple logical Citect devices, with the same physical address, then put them on the same port. |