I have two I/O Servers effectively Primary
and Standby for two PLCs. Each has an I/O Device with a Startup
Mode of Primary and Standby respectively. When a page requesting
data is displayed on the standby I/O server a hardware alarm "PLC
Server Stand-by I/O Device activated" is generated. This problem
can be caused by having a separate project for each I/O server
where the project on one I/O server does not reference the other
I/O server. At startup Citect checks the list of I/O servers and
establishes a session with each I/O server on the list. If the I/O
server is not on the list then no session is established and the
redundancy will not work. |