Summary: |
The express wizard for setting up communications with the Allen-Bradley 1784-KT,-KTX and -KTXD cards does not use the correct default values. |
Solution: |
CIT has confirmed this to be a problem in
Citect for Windows version 5.00. This problem has been fixed in
version 5.01.
There are two problems: 1. The default address is set as 1KT0,1 when it should be 1KT:0,1 2. The KTX and KTXD cards require a different I/O port address format. 0xD0 is the format required rather than 0xD000. Both these problems have been addressed in Citect V5.01 |