Applies To:
  • CitectSCADA 5.0

Summary:
I used the Express I/O Device Wizard to add an ABB Kent-Taylor Modcell unit to my project. The Address default came up as 0,1 and the Parity came up Odd_P. This is different from the Help. 

Solution:
The Communications Forms information in the Help is correct. If you use the Express I/O Device Wizard to add a Modcell, modify the Address to be a single digit, and after the Wizard is finished, go to Communications|I/O Devices and modify the Parity to be None. 