Applies To: |
|
Summary: |
I have a network with 2 computers and only one of them has a key with 1 Full Licence and 1 Display Client. The Display Client is used as a floating licence for the second computer. I have configured the Display Client with the Computer Setup Wizard, but I keep on getting "Software protection Failure". What have I done wrong? |
Solution: |
Make sure that your CITECT.INI has the
following parameter
[CLIENT] If not, Citect will try to use a floating Full Licence instead of a floating Display Client. CIT has confirmed this to be a problem in Citect for Windows versions 4.00 to 5.00. This problem will be fixed shortly. |
Keywords: |
Related Links