Applies To:
  • CitectSCADA 4.xx, 5.xx

Summary:
Can I connect Power Measurement Limited power meter devices to Citect? 

Solution:
Yes, They can be communicated to with the Modbus protocol. Multiple units can be connected to Citect over RS485.

Note : As they only have 40000 addresses, you must be using the latest Citect Modbus Driver and have the following entry in the Citect.INI file.

[MODBUS]
InitType=3

 