Applies To:
  • CitectSCADA 5.x

I have a old project in version 4 where I updated to Version 5. When I compiled the project I got heaps of errors. I noticed that that many Cicode Functions were duplicated why? 

In version 4 and earlier all the cicode files where in a listed in a file named Library.DBF. When you of some reason deleted the file with CtEdit, it only deleted the record in Libray.dbf and didn't delete the the Cicode file (Suffix CI).

In version 5 it does not use the file Library.DBF. And the old CI files still remains.

Open the file Library.dbf. Use explorer and list all the files with suffix CI. (extension). Delete the cicode files wich not are listed in the file Library.DBF