Applies To:
  • CitectSCADA 3.30, 3.40, 4.10, 4.20, 5.xx

Summary:
Can Citect communicate to Daniel Flow Computers? 

Solution:
Daniel Flow Computers use the Modbus protocol. Using Citect's MODBUS driver, Citect can communicate to the Daniel Flow Computers. The Daniel Flow Computers format of the floating point values is different to Citect's default, so a Citect.INI parameter must be employed to resolve this issue. The INI parameter is:

[MODBUS]
FloatMode=1

See also KB article Q1903

 