AB Superwho and WinLinks is able to communicate to the PLC when the KF3 module node address is set to 31 (the max for DH-485) but Citect cannot establish comms. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows version 3.xx to 5.xx. We are researching this problem and will post new information here as it becomes available. The work-around is to set the node address to 0. |