Applies To:
  • CitectSCADA 5.00

I have a dynamic object and use two keyboard commands. The first keyboard command has no privilege and the second one has a privilege associated with it. When no use is logged in no cursor will be shown on the object and the keyboard command with no privilege cannot be executed. Is this correct? I noticed if I swap the order of the commands in the configuration tab then all works as I expect it. 

This is a known problem. The cursor will only appear if the keyboard command with no privilege is defined last in the dynamic object.

CIT has confirmed this to be a problem in Citect for Windows versions 5.00. This problem has been fixed in version 5.00 Service Pack E.