Applies To: |
|
Summary: |
If you have a database with greater than 32000 points used then you will get the error 'fatal - cannot write to changes.ndx' at the end of compilation. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions 5.00 Service Pack C. This problem has been fixed in version 5.00 Service Pack E. |