Applies To:
  • CitectSCADA 5.00, 5.01

Summary:
The maximum number of animations that Citect runtime can support without anomalous behaviour is governed by the [Animator]MaxAn parameter and defaults to 1024. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions 5.0 to 5.01. This limitation has been removed in version 5.10. The animation point limit is always 32000 irrespective of the setting of the MaxAn parameter in this version of Citect runtime. The MaxAn parameter is now redundant.  

Keywords:
 

Attachments