Citect Time Stamped Alarms do not always match what the PLC reported. |
Solution: |
It appears that if more than one high
resolution alarm occurs in one scan and they are from different I/O
Devices, then Citect may complete the display and logging of the
time stamped alarms using old data - before all of the I/O Devices
have returned with their new data.
CIT has confirmed this to be a problem in Citect for Windows versions to 5.01. This problem has been fixed in version 4.20 Spk K and 5.01 Spk A. |