Applies To:
  • CitectSCADA 3.40, 4.20, 5.01

When doing a network shutdown with the Shutdown() Cicode function it is possible to use mode 6 to stop the originator of the shutdown from shutting down. However this also stops the command having an effect on any network clients and they will not shutdown.

CIT has confirmed this to be a problem in Citect for Windows versions to 5.01. This problem has been fixed in version 5.01 Service Pack A.