Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

Summary:
When TIDirect driver does a block write to V area and address is greater than 1036, the operation will fail and generate driver error 31 (0x1F). 

Solution:
This has been fixed in TIDirect driver version 2.10. 

Keywords:
 

Attachments