Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.00, 5.01, 5.10

If you use a void function (one with no return type) as the expression for Bars (V3.xx/V4.xx) or Scaling, Movement or Fill Level (V5.xx) then the compiler will not generate an error and corruption may occur at runtime. This may lead to Citect crashing. 

The compiler has been modified so that it will generate an "Incompatible types" error message in this situation.

CIT has confirmed this to be a problem in Citect for Windows versions to 5.10. This problem has been fixed in version 5.10 Service Pack A.