Applies To: |
|
Summary: |
If you quickly press history scrolling buttons on a trend client and the trend span is greater than 32000 times the display period, then the display may not be correct and the Trend Server may crash. This will be more prominent when you have recently added new trends. |
Solution: |
CIT has confirmed this to be a problem in Citect for Windows versions to 5.10. This problem has been fixed in Version 3.40/4.20 Service Pack K and Version 5.10 Service Pack A. |
Keywords: |
Related Links
Attachments