Applies To:
  • CitectSCADA 5.xx

Summary:
I am using the "Add Project Link" option on many PC's to connect to my project database which resides on a file server. However, on one of my Citect installations, when I link to the project, the standard template buttons and the Alarm animators do not appear on any of my pages at runtime. And even some popups are missing buttons. What is the problem with this one PC? 

Solution:
This behaviour is seen if your monitor is running at a different resolution to that which the project was compiled at. So make sure the resolution (Control Panel - Display) is the same for each PC running the linked project. Alternatively, recompile the project (however, this will obviously cause the same problem on another PC when you next shutdown and restart Citect). 