I am using the CTAPI point functions to access Citect tags but ctPointRead fails with error code 16406. The device is online, what is going wrong? |
Solution: |
This problem may occur when redundant I/O
Devices are configured such that the Standby device appears before
the Primary in the devices database. If you experience this
problem, it can be resolved by reordering the I/O Device records to
place the Primary devices ahead of the Standby devices.
CIT has confirmed this to be a problem in Citect for Windows versions 5.10 to 5.10A. This problem has been fixed in version 5.20. |