Applies To:
  • CitectSCADA 5.xx

When loading a page in Graphics Builder or Citect Runtime, an error message box may appear with the following text (the text where xxxx varies between versions):

Error: File ( xxxx\source\api\ctg\ctg_obj.c )

Line xxxx - to much object data to read


This problem is caused by either a corrupt page or corrupt library objects that are referenced by the page.

The only solution is to recreate the corrupted library object or page and re-save it. This problem may be related to a previous problem where objects may get corrupted during a save in Graphics Builder, which was fixed in Citect for Windows version 5.10 Service Pack A.