Applies To: |
|
Summary: |
Ever since I upgraded Siemens S7-5412 library from version 1.1 to version 4.1.6.2, I have found that I am not able to do a bit write any more (I am using Citect Sseven driver version 2.14). |
Solution: |
The problem is due to incompatibility between the Siemens' libraries. CIT has confirmed this to be a problem in Sseven driver versions up to 2.14 and it has been fixed in version 2.17. |
Keywords: |
Related Links
Attachments