Is it possible to communicate from Citect over a TCP/IP Ethernet LAN to a gateway which has an IP address and converts the signal to serial which in turn is connected to PLCs? |
Solution: |
Yes. A possible solution is to use
Stallion's LantraServer as the 'Gateway'. It will allow you to
create a virtual COM port on the Citect I/O Server which is
redirected over the Ethernet TCP/IP network to the gateway, and
then via the normal serial connection to the device (eg. PLC etc.).
Please contact Stallion for further details, or refer to their web site (http://www.stallion.com/html/lantraserver.html). |