Applies To:
  • CitectSCADA 5.xx

StrToDate() and FileGetTime() may return times which are one hour out when used for dates between the rollover date for daylight saving and the end of the same month - this will occur at both ends of daylight saving.


In Australia daylight saving starts on Sunday 26th October at 2:00am. With dates occuring during the period 26th October to 31st October (inclusive), both StrToDate() and FileGetTime() will be one hour out.


CIT has confirmed this to be a problem in Citect for Windows versions 5.XX. This problem has been fixed in version 5.10 Service Pack C.