Applies To:
  • CitectSCADA 4.xx, 5.xx

Summary:
When I run the Computer Setup Wizard in custom mode, it does not show me the I/O server and events from my included projects. Please explain. 

Solution:
The Custom Setup Wizard was implemented to access only the main project. During compilation, most everything from included projects is compiled into the main project files and this is where the project is run. In particular, I/O server and named Events from included projects are not seen by the custom wizard. If you have configured these in an included project you must edit the Citect configuration file (default is "Citect.ini" in the Windows directory). 

Keywords:
 