Applies To:
  • CitectSCADA 3.xx, 4.xx, 5.xx

Summary:
Digital arrays which span a multiple of the protocol blocking constant will not read correctly. For the generic protocol the blocking constant is 1024 bits, so any array spanning 1024, 2048, 3072, etc. will read incorrectly. Thus the array D993[32] will not read correctly. 

Solution:
CIT has confirmed this to be a problem in Citect for Windows versions to 5.XX. This problem has been fixed in version 5.20 Service Pack B. 

Keywords:
 

Attachments